공공의료시설에 적합한 신재생에너지시스템의 복합적용비율에 관한 연구

Title
공공의료시설에 적합한 신재생에너지시스템의 복합적용비율에 관한 연구
Other Titles
A Study on the Application Ratio by the New and Renewable Energy Systems Fit for Public Medical Facilities
Author(s)
조영흠홍준호[홍준호]이용호[이용호]황정하[황정하]
Keywords
KeyWords : 공공의료시설(The Public medical facility); 신재생에너지시스템(Renewable energy system); 경제성(The Economy Analysis); 기술성(The technical Analysis); 환경성(The Environment Analysis)
Issue Date
201404
Publisher
한국태양에너지학회
Citation
한국태양에너지학회 논문집, v.34, no.2, pp.32 - 43
Abstract
Abstract : This study set out to identify the importance of each factor influencing facility selection with a survey among public medical facilities under the category of public buildings and apply the importance of economy, technology and environment with the weighting factor method, thus proposing optimal application plans. The research content of each section can be summarized as follows: 1) Estimated energy consumption according to the energy simulation was 65,129MWh/yr, which was 18.7% higher than that according to the calculation equation. Of the energy consumption, more than 80% was used by heating and cooling facilities and construction facilities, and 20% was used by electronics such as medical equipments and in and outdoor lighting. 2) The results of a survey on the factors influencing the importance when selecting a new and renewable energy system reveal that the upper items had a priority in economy, environment, and technology in the descending order and that the lower items had a priority in initial investments, maintenance and repair costs=energy costs, supply reliability, energy efficiency and CO₂emissions in the descending order.3) The application alternatives were analyzed in economy, technology, and environment. As a result, a geothermal system turned out to be the most excellent one across all the upper and lower comparison items. Of the other systems, a solar thermal system was superior in initial investments, maintenance and repair costs, and energy efficiency, whereas a photovoltaic system was superior in energy costs, supply reliability, and CO₂emissions. 4) As for the mixed application ratio among economy, technology, and environment, when the percentage of a geothermal system was approximately 80% or higher in a new and renewable energy system, it was the best and most optimal application plan.
URI
http://hdl.handle.net/YU.REPOSITORY/32400
ISSN
1598-6411
Appears in Collections:
건축학부 > 건축학부 > Articles
Files in This Item:
There are no files associated with this item.
Export
RIS (EndNote)
XLS (Excel)
XML


qrcode

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

BROWSE