에너지 효율향상을 위한 VAV 시스템 선정과 적정 최소풍량에 관한 연구

Title
에너지 효율향상을 위한 VAV 시스템 선정과 적정 최소풍량에 관한 연구
Other Titles
A Study on the Selection of the VAV System and Proper Minimum Airflow to Improve Energy Efficiency
Author(s)
김효준정영주서동현[서동현]조영흠
Keywords
VAV system; Minimum airflow; Terminal box; Building Energy; Energyplus
Issue Date
201312
Publisher
한국생활환경학회
Citation
한국생활환경학회지, v.20, no.7, pp.906 - 912
Abstract
In the VAV system, proper minimum airflow is an essential factor in IAQ and energy efficiency. However,it is hard to use VAV system effectively in the domestic industry because of lack of systematic study and management. In this study, we selected the building used as office and then changed the system and minimum airflow to increasethe efficiency of VAV system. In the simulation, Energyplus was used. We set the existing system, VAV without reheatsystem+convector as CASE1, VAV with reheat system as CASE2 and a system which applied proper minimum airflowto CASE2 as CASE3. As a result, the quality of indoor air was all satisfied and total energy consumption decreasedby about 23%.